KYN 61-40.5 Series Switchgear(HV)
• Ambient temperature: -15°C to +40°C• Altitude: ≤ 2000m • Humidity: ≤ 95% (daily), ≤ 90% (monthly)• Seismic resistance: ≤ 8 magnitude• Suitable for non-corrosive, non- flammable environments
Service Conditions
• Ambient temperature: -15°C to 40°C
• Altitude: ≤ 2000m • Humidity: ≤ 95% (daily), ≤ 90% (monthly)
• Seismic resistance: ≤ 8 magnitude
• Suitable for non-corrosive, non- flammable environments
Main Technical Parameters
| Name | Unit | Data | |
|---|---|---|---|
| Rated voltage | kV | 40.5 | |
| Rated current | Rated current of mainbus | A | 630、1250、1600 |
| Rated current of circuit breaker | A | 630、1250、1600 | |
| Rated insulation level | 1 minutes power frequency withstand voltage between poles, between pole and earth/between fractures | kV | 95/110 |
| Lightning impulse withstand voltage(peak), between poles, between pole and earth/between fractures | kV | 185/215 | |
| Power frequency withstand voltage of auxiliary circuit and control circuit | V/min | 2000 | |
| Rated frequency | Hz | 50 | |
| Rated short circuit breaking current | kA | 20、25、31.5 | |
| Rated short time withstand current / Rated short circuit duration | kA/4s | 20、25、31.5 | |
| Rated peak withstand current | kA | 50、63、80 | |
| Rated short circuit of closing current | kA | 50、63、80 | |
| Rated voltage of control circuit | v | DC:110,220
AC:110,220
|
|
| Protection level | Switchgear housing | / | IP4X |
| Compartment (when the switchgear door is open) | / | IP2X | |